DIMENSIONS
Height to top of lid 15 1/8”
Overall height 16 3/4”
Width at bottom 11 1/8”
Width at top 12 1/16”
Depth at bottom 9 7/16”
Depth at top 10 1/16”
As the applied Electromagnetic Field (EMF) across the cell terminals increases, current flow through the Kirk Cell will increase in general agreement with the data in the Performance tables below. Actual current flow will vary with ambient conditions including but not limited to: temperature, solution concentration and age.
K-50 KIRK CELL PERFORMANCE TABLE
Delta E Apparent
Across Cell Resultant Internal
Terminals Current Impedance
(Volts) Flow (Ohms)
_________________________________________________________________
DIRECT CURRENT DATA
0.15 100ua 1500
0.38 1ma 380
0.42 2ma 210
0.45 3ma 150
0.46 4ma 115
0.48 5ma 96
0.50 6ma 83
0.52 7ma 74
0.53 8ma 66
0.55 9ma 61
0.59 10ma 59
0.69 15ma 46
0.86 20ma 43
0.925 25ma 37
1.00 30ma 33
1.16 40ma 29
1.20* 50ma 24
1.30 100ma 13
1.72 500ma 3.4
1.76 1A 1.8
1.82 5A 0.36
1.85 10A 0.19
2.15 100A 0.022
2.65 500A 0.053
3.15 1KA 0.0032
ALTERNATING CURRENT DATA
0.01 500ma 0.02
0.02 1A 0.02
0.04 5A 0.01
0.20 10A 0.02
0.58 50A 0.012
0.62 100A 0.0062
1.30 500A 0.0026
10.6 14KA 0.00076
12.5 38.5KA 0.00032
14.0 44.0KA 0.00032
15.0 52.5KA 0.00029
17.0 58.0KA 0.00029
19.9 64.0KA 0.00031
*Leakage threshold |