K-5 A

K-25

K-50

DIMENSIONS

Height to top of lid                 15 1/8”
Overall height                       16 3/4”
Width at bottom                    11 1/8”
Width at top                          12 1/16”
Depth at bottom                    9 7/16”
Depth at top                          10 1/16”

As the applied Electromagnetic Field (EMF) across the cell terminals increases, current flow through the Kirk Cell will increase in general agreement with the data in the Performance tables below. Actual current flow will vary with ambient conditions including but not limited to: temperature, solution concentration and age.

K-50 KIRK CELL PERFORMANCE TABLE

Delta E                                                                                    Apparent
Across Cell                             Resultant                                 Internal
Terminals                               Current                                    Impedance
(Volts)                                     Flow                                        (Ohms)
_________________________________________________________________

DIRECT CURRENT DATA


0.15                                         100ua                                      1500
0.38                                         1ma                                         380
0.42                                         2ma                                         210
0.45                                         3ma                                         150
0.46                                         4ma                                         115
0.48                                         5ma                                         96
0.50                                         6ma                                         83
0.52                                         7ma                                         74
0.53                                         8ma                                         66
0.55                                         9ma                                         61
0.59                                         10ma                                       59
0.69                                         15ma                                       46
0.86                                         20ma                                       43
0.925                                       25ma                                       37
1.00                                         30ma                                       33
1.16                                         40ma                                       29
1.20*                                       50ma                                       24
1.30                                         100ma                                     13
1.72                                         500ma                                     3.4
1.76                                         1A                                           1.8
1.82                                         5A                                           0.36
1.85                                         10A                                         0.19
2.15                                         100A                                       0.022
2.65                                         500A                                       0.053
3.15                                         1KA                                        0.0032

ALTERNATING CURRENT DATA

0.01                                         500ma                                     0.02
0.02                                         1A                                           0.02
0.04                                         5A                                           0.01
0.20                                         10A                                         0.02
0.58                                         50A                                         0.012
0.62                                         100A                                       0.0062
1.30                                         500A                                       0.0026
10.6                                         14KA                                      0.00076
12.5                                         38.5KA                                   0.00032
14.0                                         44.0KA                                   0.00032
15.0                                         52.5KA                                   0.00029
17.0                                         58.0KA                                   0.00029
19.9                                         64.0KA                                   0.00031

*Leakage threshold

  KIRK ENGINEERING COMPANY, INC.
  202 C Street North
  Oneonta, Alabama 35121 USA
  Phone : 205-274-2221
  Fax : 205-274-7644
  eMail : kirkengineering@otelco.net